Tech Specs
|
|
|
|
Specifications
The Sun Modular Datacenter is the only containerized datacenter certified for regulatory and safety compliance as well as for fire-suppression in over 50 countries. With installations on nearly every continent, it is an ideal solution for customers in emerging markets who need a fast, economical, and environmentally sound way to increase their datacenter capacity.
Key Specifications
- Configurable up to 8 racks (19" w x 30.75" d payload dimensions)
- Can cool up to 25kW per rack
- Compatible with Sun or third party gear
- -29°C to 54°C (-20°F to 130°F) operating range
|
|
Dimensions and Weight |
| Length |
6.06m (20 feet) |
|
| Width |
2.44m (8 feet) |
|
| Height |
2.59m (8 feet 6 inches) |
|
| Shipping Weight (no payload) |
<8,165 kg (<18,000 lb.) |
|
| Maximum Weight |
<15,422 kg (<34,000 lb.) |
Capacity |
| Rack Quantity |
- S20 – Eight racks: seven for payload and one for network and internal control equipment
- D20 – Seven racks: six for payload and one for network and internal control equipment
|
|
| Rack Units (RU) |
- 40 RU per rack
- 280 RU in S20, 240 RU in D20 available for IT equipment
- 25 RU available for network equipment in the infrastructure rack
- 15 RU reserved for Sun MD monitoring, management, and control equipment
|
|
| Rack Dimensions |
EIA/ANSI (RETMA) standard 19-inch (48.26 cm) EIA RS-310-D
|
|
| Height (usable) |
177.9 cm (70 inches) |
|
| Depth (usable) |
S20 – 78.1 cm (30.75 in.) all racks
D20 – 78.1 cm (30.75 in.) racks # 1- 4
D20 – 115 cm (45.25 in.) racks # 5 - 7 |
|
| Width (usable) |
48.26 cm (19 inches) |
|
| Load capacity per rack |
862 kg (1900 lb.) |
|
| Power per rack |
12.5kW standard per rack; 25kW "high power option" for payload racks |
Power Options |
| Low Voltage Configuration |
North America/Japan
Input Voltage: 110/190 - 127/220 VAC, 3 Phase, 50/60 Hz, 600a per panel
Internally Distributed Voltage: 110 - 127 VAC, 1 Phase and 190-220 VAC, 3 Phase, 50/60 Hz (Internal single phase not accessible)
|
|
| High Voltage Configuration |
International
Input Voltage: 220/380 - 240/415 VAC, 3 Phase, 50/60 Hz, 300a per panel
Internally Distributed Voltage: 220-240 VAC, 1 Phase and 220/380 - 240/415 VAC, 3 Phase, 50/60 Hz (Internal single phase not accessible)
|
External Network Connections |
| Two network panels supported (choice of one option for each side) |
Network Panel Options:
- RJ-45 network panel (8 x RJ-45 connectors)
- LC Fibre network panel (8 x LC fibre connectors - single or multi mode)
- RJ-45/LC Fibre network panel (4 x RJ-45 and 4 x LC fibre - single or multi mode)
- Bulk cable pass-through panel
|
Environmental |
| External temperature and humidity deployment range (doors closed) |
-29°C to 54°C (-20°F to 130°F), up to 100% humidity |
|
| Internal operating temperature and humidity (doors closed) |
10°C to 35°C (50°F to 95°F) and 20% to 80% relative humidity (RH), noncondensing
|
|
| Altitude |
3048 m (10,000 ft) or lower depending on payload maximum |
|
| Noise |
56.0 dBA (external at 2 m)
78.5 dBA (internal at nominal load) |
External Water Connectivity |
| Water Hook-ups (each side) |
50 mm (2 in.) supply and return |
|
| Water Pressure |
50 PSIG nominal, 80 PSIG maximum.
|
|
| Water Flow and Temperature |
170 to 246 LPM (45 to 65 GPM), 18°C to 22°C (64°F to 71°F) nominal |
Regulations (meets or exceeds the following requirements when deployed) |
Safety |
- UL 60950-1 (ETL classification marking)
- UL 50, Ed. 11 (NEMA 3R equivalent levels)
- Russia GOST R
- CB Scheme with national differences
- CAN/CSA C22.2 No. 60950-1
- EN 60950-1
- CENELEC EN 60529 (IP-44 levels)
|
|
| RFI/EMI |
- EN 55022 (Sun MD and payload)
- VCCI (Sun MD and payload)
- AS/NZS 3548 (Sun MD and payload)
- Korea MIC (Sun MD and payload)
- Russia GOST R (Sun MD and payload)
Payload relevant testing
- CFR47, Part 15, FCC Class A
- ICES-003 Class A
- CNS-13438
|
|
| Immunity |
- EN 55024
- Korea MIC
- Russia GOST R
|
Certifications |
| Safety |
CE Mark, GOST, ETL Classified, CB Report with National Differences
|
|
| EMC |
CE Mark, ITS Technical Construction File, C-Tick, GOST-R, MIC |
|
| ROHS |
RoHS-compliant (with lead-in solder exemption) for control & management equipment
|
|