AMPs Redundant
|
32A (2x16)
|
24A
|
42A (3x14)
|
96A (3x32)
|
78A (3x26)
|
|
AMPS Non-Redundant
|
64A (4x16)
|
48 (2x24)
|
84A (6x14)
|
192 (6x32)
|
156 (6x26A)
|
|
# of outlets to support the products inside the rack
|
48
|
72
|
72
|
72 (900-36N supports only 68 outlets)
|
72 (900-36N supports only 68 outlets)
|
|
# of RUs used within the rack
|
0
|
2
|
2
|
2
|
2
|
|
# of inputs per power option
|
4 inputs
|
2 inputs
|
2 inputs
|
2 inputs
|
2 inputs
|
|
Geography
|
Choice of domestic or international external power cords
|
Americas, Japan, Taiwan
|
Americas, Japan, Taiwan
|
EMEA, APAC except Japan & Taiwan
|
Americas, Japan, Taiwan
|
|
Datacenter Considerations
|
4 x 20A/16A circuits are required
|
2 x 30A circuits are required
|
2 x 30A three-phase four wire circuits are required
|
2 x 32A three-phase five wire circuits are required
|
2 x 60A three-phase four wire circuits are required
|
|
AC Power Receptacle
|
Domestic NEMA L6-20R International IEC 309 16A 3 Position
|
NEMA L6-30R
|
NEMA L15-30R
|
IEC 309 32A 5 Position
|
IEC 309 60A 4 Position
|
|
Build to Order Power Module Part Number
|
5142A (for 900-38, 1000-38), 5143A (for 9000-36N), 9236A-2 for 1000-42
|
9241A (900-36N not supported)
|
9243A (900-36N not supported)
|
9245A
|
9247A
|
| |
|
Sun Rack 900-38, Alloy Door
|
SR2-2938-XPDS
|
None
|
None
|
None
|
None
|
|
Sun Rack 1000-38, Alloy Door
|
SR2-21038-XPDS
|
None
|
None
|
None
|
None
|
|
Sun Rack 1000-42, Alloy Door
|
SR2-21042-XPDS
|
SR2-21042-X30SPL
|
None
|
SR2-21042-X32TPL
|
SR2-21042-X60TPL SR2-21042-X60A60 (2 x 60A MPS)
|
|
Sun Rack 900-36N
|
SR9-2XBM036A-IP (Purple Door)
|
None
|
None
|
None
|
None
|