AMPs Per PDU
|
24A
|
24A
|
48A (2X24)
|
72A (3X24)
|
69A (3X23A)
|
120A (6x20)
|
180A (9x20)
|
|
Outlets
|
14 C13 and 2 C19
|
42 C13 and 6 C19
|
42 C13 and 6 C19
|
42 C13 and 6 C19
|
42 C13 and 6 C19
|
42 C13 and 6 C19
|
45 C13 and 9 C19
|
|
Number of Inputs
|
1 30A 1ph
|
1 30A 1ph
|
2 30A 1ph
|
3 30A 1ph
|
1 60A 3ph
|
2 60A 3ph
|
3 60A 3ph
|
|
Current
|
24A
|
24A max
|
24A max per input
|
24A max per input
|
40A max per phase
|
34.6A max per phase
|
34.6A max per phase
|
|
Data Center Receptacle
|
NEMA L6-30P
|
NEMA L6-30R
|
NEMA L6-30R
|
NEMA L6-30R
|
IEC309- 3P4W-IP67 60A 250VAC 3ph
|
IEC309- 3P4W-IP67 60A 250VAC 3ph
|
IIEC309- 3P4W-IP67 60A 250VAC 3ph
|
|
Metering
|
None
|
Phase Current
|
Phase Current
|
Phase Current
|
Phase Current
|
Phase Current
|
Phase Current
|
|
Max Per Rack
|
6
|
2
|
2
|
2
|
2
|
2
|
2
|
|
Part Number
|
XSR-5K-L630CP
|
XSR-5K-L630
|
XSR-10K-L630
|
XSR-15K-L630
|
XSR-15K- IEC309-4P
|
XSR-24K- IEC309-4P
|
XSR-37K- IEC309-4P
|
|
Rack Models Supported
|
1042, 1042E, 1242, 1242E
|
1042, 1042E, 1242, 1242E
|
1042, 1042E, 1242, 1242E
|
1042, 1042E, 1242, 1242E
|
1242, 1242E
|
1242, 1242E
|
1242, 1242E
|
|
| |
|
|
|
|
|
|
|
|
AMPs Per PDU
|
24A
|
24A
|
48A (2X24)
|
72A (3X24)
|
62.7A (3X20.9A)
|
109A (6x18.1)
|
163A (9x18.1)
|
|
Outlets
|
14 C13 and 2 C19
|
42 C13 and 6 C19
|
42 C13 and 6 C19
|
42 C13 and 6 C19
|
42 C13 and 6 C19
|
42 C13 and 6 C19
|
45 C13 and 9 C19
|
|
Number of Inputs
|
1 25A 1ph
|
1 25A 1ph
|
2 25A 1ph
|
3 25A 1ph
|
1 25A 3ph
|
2 25A 3ph
|
3 25A 3ph
|
|
Current
|
25A max
|
25A max
|
25A max per input
|
25A max per input
|
25A max per phase
|
18A max per phase
|
18A max per phase
|
|
Data Center Receptacle
|
IEC309- 2P3W-IP44 32A 250VAC
|
IEC309- 2P3W-IP44 32A 250VAC
|
IEC309- 2P3W-IP44 32A 250VAC
|
IEC309- 2P3W-IP44 32A 250VAC
|
IEC309- 4P5W-IP44 32A 400VAC 3ph
|
IEC309- 4P5W-IP44 32A 400VAC 3ph
|
IEC309- 4P5W-IP44 32A 400VAC 3ph
|
|
Metering*
|
None
|
Phase Current
|
Phase Current
|
Phase Current
|
Phase Current
|
Phase Current
|
Phase Current
|
|
Max Per Rack
|
6
|
2
|
2
|
2
|
2
|
2
|
2
|
|
Part Number
|
XSR-5K-IEC309CP
|
XSR-5K- IEC309
|
XSR-10K- IEC309
|
XSR-15K- IEC309
|
XSR-15K- IEC309-5P
|
XSR-24K- IEC309-5P
|
XSR-37K- IEC309-5P
|
|
Rack Models Supported
|
1042, 1042E, 1242, 1242E
|
1042, 1042E, 1242, 1242E
|
1042, 1042E, 1242, 1242E
|
1042, 1042E, 1242, 1242E
|
1242, 1242E
|
1242, 1242E
|
1242, 1242E
|
|
*Sun Rack II PDUs contain a metering unit that allows you to monitor
the current (in amperes) being used by the equipment connected to the PDU.
Monitoring Functionality:
- Metering of current (in amperes) per phase
- Current can be monitored by viewing the LCD screen on the PDU itself or remotely from a system on the network
- Connection to the network using DHCP or Static IP protocols
- HTML interface and SNMP capability
- Ability to set thresholds to generate alarm if amp reading reaches the threshold level
- Ability to send messages to systems on the network
- Access rights/user management
- Remote firmware upgrade via HTML
|